品牌
代理商厂商性质
上海所在地
· 用于连接 LOGO! 的扩展模块模块化
· 带数字量输入和输出、模拟量输入或模拟量输出
· 继电器输出,输出电流为 5A。
· 不同的模块:
o 4 点数字量输入,4 点数字量输出;或
o 4 点数字量输入,4 点继电器输出;或
o 2 点模拟量输入;或
o 2 模拟量输出。
· 用于连接到 LOGO! 模块化逻辑模块的接口。
关于兼容性的说明:
LOGO! 的扩展模块8 只能在 LOGO! 上使用8 个基本设备!
LOGO! 的扩展模块6 和 7 不能与 LOGO! 结合使用8 个基本设备。
Article number | 6ED1055-1CB00-0BA2 | 6ED1055-1HB00-0BA2 | 6ED1055-1MB00-0BA2 | 6ED1055-1FB00-0BA2 |
LOGO! DM8 24 EXPANSION MODULE, | LOGO! DM8 24R EXPANSION MODULE, | LOGO! DM8 12/24R, EXP. MODULE | LOGO! DM8 230R, EXP. MODULE, | |
Installation type/mounting | ||||
Mounting | on 35 mm DIN rail, 2 spacing units wide | on 35 mm DIN rail, 2 spacing units wide | on 35 mm DIN rail, 2 spacing units wide | on 35 mm DIN rail, 2 spacing units wide |
Supply voltage | ||||
Rated value (DC) | ||||
· ● 12 V DC | Yes | |||
· ● 24 V DC | Yes | Yes | Yes | |
· ● 115 V DC | Yes | |||
· ● 230 V DC | Yes | |||
permissible range, lower limit (DC) | 20.4 V | 20.4 V | 10.8 V | 100 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 253 V |
Rated value (AC) | ||||
· ● 24 V AC | Yes | |||
· ● 115 V AC | Yes | |||
· ● 230 V AC | Yes | |||
Line frequency | ||||
· ● permissible range, lower limit | 47 Hz | 47 Hz | ||
· ● permissible range, upper limit | 63 Hz | 63 Hz | ||
Digital inputs | ||||
Number of digital inputs | 4 | 4 | 4 | 4 |
Input voltage | ||||
· ● Type of input voltage | DC | AC/DC | DC | AC/DC |
· ● for signal "0" | < 5 V DC | < 5 V AC/DC | < 5 V DC | < 40 V AC, < 30 V DC |
· ● for signal "1" | > 12 V DC | > 12 V AC/DC | > 8.5 V | > 79 V AC, > 79 V DC |
Input current | ||||
· ● for signal "0", max. (permissible quiescent current) | 0.88 mA | 1.1 mA | 0.88 mA | 0.06 mA; 0.05 mA with AC, 0.06 mA with DC |
· ● for signal "1", typ. | 2.1 mA | 2.63 mA | 1.5 mA | 0.13 mA |
Input delay (for rated value of input voltage) | ||||
for standard inputs | ||||
· — at "0" to "1", max. | 1.5 ms | 1.5 ms | 1.5 ms | 40 ms |
· — at "1" to "0", max. | 1.5 ms | 15 ms | 1.5 ms | 75 ms |
Digital outputs | ||||
Number of digital outputs | 4 | 4; Relays | 4; Relays | 4; Relays |
Short-circuit protection | Yes | No | No | No |
Controlling a digital input | Yes | Yes | Yes | |
Switching capacity of the outputs | ||||
· ● on lamp load, max. | 1 000 W | 1 000 W | 1 000 W; 500 W at 115V AC | |
Output current | ||||
· ● for signal "1" rated value | 0.3 A | 5 A | 5 A | 5 A |
· ● for signal "1" minimum load current | 100 mA | 100 mA | 100 mA | |
Parallel switching of two outputs | ||||
· ● for uprating | No | No | No | No |
Switching frequency | ||||
· ● with resistive load, max. | 10 Hz | 2 Hz | 2 Hz | 2 Hz |
· ● with inductive load, max. | 0.5 Hz | 0.5 Hz | 0.5 Hz | 0.5 Hz |
· ● mechanical, max. | 10 Hz | 10 Hz | 10 Hz | |
Relay outputs | ||||
Switching capacity of contacts | ||||
· — with inductive load, max. | 3 A | 3 A | 3 A | |
· — with resistive load, max. | 5 A | 5 A | 5 A | |
EMC | ||||
Emission of radio interference acc. to EN 55 011 | ||||
· ● Limit class B, for use in residential areas | Yes | Yes | Yes | Yes |
Degree and class of protection | ||||
Degree of protection acc. to EN 60529 | ||||
· ● IP20 | Yes | Yes | Yes | Yes |
Standards, approvals, certificates | ||||
CE mark | Yes | Yes | Yes | Yes |
CSA approval | Yes | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes | Yes |
developed in accordance with IEC 61131 | Yes | Yes | Yes | Yes |
according to VDE 0631 | Yes | Yes | Yes | |
Marine approval | Yes | Yes | Yes | Yes |
Ambient conditions | ||||
Ambient temperature during operation | ||||
· ● min. | 0 °C | 0 °C | 0 °C | 0 °C |
· ● max. | 55 °C | 55 °C | 55 °C | 55 °C |
Dimensions | ||||
Width | 35.5 mm | 35.5 mm | 35.5 mm | 35.5 mm |
Height | 90 mm | 90 mm | 90 mm | 90 mm |
Depth | 58 mm | 58 mm | 58 mm | 58 mm |
Article number | 6ED1055-1CB10-0BA2 | 6ED1055-1NB10-0BA2 | 6ED1055-1FB10-0BA2 |
LOGO! DM16 24, EXP. MODULE | LOGO! DM16 24R, EXP. MODULE, | LOGO! DM16 230R, EXP. MODULE, | |
Installation type/mounting | |||
Mounting | on 35 mm DIN rail, 4 spacing units wide | on 35 mm DIN rail, 4 spacing units wide | on 35 mm DIN rail, 4 spacing units wide |
Supply voltage | |||
Rated value (DC) | |||
· ● 24 V DC | Yes | Yes | |
· ● 115 V DC | Yes | ||
· ● 230 V DC | Yes | ||
permissible range, lower limit (DC) | 20.4 V | 20.4 V | 100 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 253 V |
Rated value (AC) | |||
· ● 24 V AC | No | ||
· ● 115 V AC | Yes | ||
· ● 230 V AC | Yes | ||
Line frequency | |||
· ● permissible range, lower limit | 47 Hz | ||
· ● permissible range, upper limit | 63 Hz | ||
Digital inputs | |||
Number of digital inputs | 8 | 8 | 8 |
Input voltage | |||
· ● Type of input voltage | DC | DC | AC/DC |
· ● for signal "0" | < 5 V DC | < 5 V DC | < 40 V AC, < 30 V DC |
· ● for signal "1" | > 12 V DC | > 12 V DC | > 79 V AC, > 79 V DC |
Input current | |||
· ● for signal "0", max. (permissible quiescent current) | 0.85 mA | 0.85 mA | 0.06 mA; 0.05 mA with AC, 0.06 mA with DC |
· ● for signal "1", typ. | 3.5 mA | 2 mA | 0.13 mA |
Input delay (for rated value of input voltage) | |||
for standard inputs | |||
· — at "0" to "1", max. | 1.5 ms | 1.5 ms | 40 ms |
· — at "1" to "0", max. | 1.5 ms | 1.5 ms | 75 ms |
Digital outputs | |||
Number of digital outputs | 8 | 8; Relays | 8; Relays |
Short-circuit protection | Yes | No | No |
Controlling a digital input | Yes | Yes | Yes |
Switching capacity of the outputs | |||
· ● on lamp load, max. | 1 000 W | 1 000 W; 500 W at 115V AC | |
Output current | |||
· ● for signal "1" rated value | 0.3 A | 5 A | 5 A |
· ● for signal "1" minimum load current | 100 mA | 100 mA | |
Parallel switching of two outputs | |||
· ● for uprating | No | No | No |
Switching frequency | |||
· ● with resistive load, max. | 10 Hz | 2 Hz | 2 Hz |
· ● with inductive load, max. | 0.5 Hz | 0.5 Hz | 0.5 Hz |
· ● mechanical, max. | 10 Hz | 10 Hz | |
Relay outputs | |||
Switching capacity of contacts | |||
· — with inductive load, max. | 3 A | 3 A | |
· — with resistive load, max. | 5 A | 5 A | |
EMC | |||
Emission of radio interference acc. to EN 55 011 | |||
· ● Limit class B, for use in residential areas | Yes | Yes | Yes |
Degree and class of protection | |||
Degree of protection acc. to EN 60529 | |||
· ● IP20 | Yes | Yes | Yes |
Standards, approvals, certificates | |||
CE mark | Yes | Yes | Yes |
CSA approval | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes |
developed in accordance with IEC 61131 | Yes | Yes | Yes |
according to VDE 0631 | Yes | Yes | Yes |
Marine approval | Yes | Yes | Yes |
Ambient conditions | |||
Ambient temperature during operation | |||
· ● min. | 0 °C | 0 °C | 0 °C |
· ● max. | 55 °C | 55 °C | 55 °C |
Dimensions | |||
Width | 71.5 mm | 71.5 mm | 71.5 mm |
Height | 90 mm | 90 mm | 90 mm |
Depth | 58 mm | 58 mm | 58 mm |
Article number | 6ED1055-1MA00-0BA2 | 6ED1055-1MD00-0BA2 |
LOGO! AM2 EXPANSION MODULE, | LOGO! AM2 RDT, 2AI, -50..+200DECR/C | |
Installation type/mounting | ||
Mounting | on 35 mm DIN rail, 2 spacing units wide | on 35 mm DIN rail, 2 spacing units wide |
Supply voltage | ||
Rated value (DC) | ||
· ● 12 V DC | Yes; 10.8 V DC to 28.8 V DC | Yes; 10.8 V DC to 28.8 V DC |
· ● 24 V DC | Yes; 10.8 V DC to 28.8 V DC | Yes; 10.8 V DC to 28.8 V DC |
Analog inputs | ||
Number of analog inputs | 2 | 2; 2 or 3 wire connection |
Input ranges | ||
· ● Voltage | Yes | No |
· ● Current | Yes | No |
· ● Resistance thermometer | No | Yes; For PT100/PT1000 sensors |
Input ranges (rated values), voltages | ||
· ● 0 to +10 V | Yes | No |
Input ranges (rated values), currents | ||
· ● 0 to 20 mA | Yes; 0 mA or 4 mA to 20 mA | No |
Input ranges (rated values), resistance thermometer | ||
· ● Pt 100 | No | Yes |
EMC | ||
Emission of radio interference acc. to EN 55 011 | ||
· ● Limit class B, for use in residential areas | Yes | Yes |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
· ● IP20 | Yes | Yes |
Standards, approvals, certificates | ||
CE mark | Yes | Yes |
CSA approval | Yes | Yes |
UL approval | Yes | Yes |
FM approval | Yes | Yes |
developed in accordance with IEC 61131 | Yes | Yes |
according to VDE 0631 | Yes | |
Marine approval | Yes | Yes |
Ambient conditions | ||
Ambient temperature during operation | ||
· ● min. | 0 °C | 0 °C |
· ● max. | 55 °C | 55 °C |
Dimensions | ||
Width | 35.5 mm | 35.5 mm |
Height | 90 mm | 90 mm |
Depth | 58 mm | 58 mm |
Article number | 6ED1055-1MM00-0BA2 |
LOGO! AM2 AQ, 2AQ, 0-10V, 0/4-20MA | |
Installation type/mounting | |
Mounting | on 35 mm DIN rail, 2 spacing units wide |
Supply voltage | |
Rated value (DC) | |
· ● 12 V DC | No |
· ● 24 V DC | Yes |
Analog outputs | |
Number of analog outputs | 2 |
Output ranges, voltage | |
· ● 0 to 10 V | Yes |
Output ranges, current | |
· ● 0 to 20 mA | Yes |
· ● 4 mA to 20 mA | Yes |
EMC | |
Emission of radio interference acc. to EN 55 011 | |
· ● Limit class B, for use in residential areas | Yes |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
· ● IP20 | Yes |
Standards, approvals, certificates | |
CE mark | Yes |
CSA approval | Yes |
UL approval | Yes |
FM approval | Yes |
developed in accordance with IEC 61131 | Yes |
according to VDE 0631 | Yes |
Marine approval | Yes |
Ambient conditions | |
Ambient temperature during operation | |
· ● min. | 0 °C |
· ● max. | 55 °C |
Dimensions | |
Width | 35.5 mm |
Height | 90 mm |
Depth | 58 mm |