Peppers铠装防爆格兰密封接头(CR系列)
Peppers防爆格兰代理商:上海颐品自动化科技有限公司
关键词:Peppers防爆格兰,Peppers防爆密封接头,Peppers防爆填料函
Peppers铠装防爆格兰,Peppers铠装防爆密封接头,Peppers防爆填料函
Peppers防爆堵头,Peppers防爆变径接头,Peppers防爆呼吸阀格兰堵头
Peppers防爆格兰等产品规格书及相关证书-请咨询上海颐品自动化科技有限公司
Peppers cable gland Product Type CR
IP Rating: IP66 & IP68 (50 metres-7 Days), Type 4X & DTS01:1991
Operating Temp: Neoprene Seals -35°C to +90°C;Silicone Seals -60°C to +180°C
Materials: Brass or Stainless Steel
Plating: Electroless Nickel
Certificates: ABS, ATEX, CCC, CCoE, CEC, EAC, IECEx, INMETRO, KCS, LLOYDS,NEC, RS,
----- Aluminium Wire Armour (AWA)
----- Single Wire Armour (SWA),
----- Steel Tape Armour (STA),
----- Steel Wire Braid (SWB),
----- Tray Cable, RMOUR CLAMPING
CR type Description:
CR type cable glands are certified Flameproof Ex db, Increased Safety Ex eb, Restricted Breathing Ex nR and Dust Protected Ex ta. They are suitable for use in Zone 1 and 2, for Gas Groups IIA, IIB and IIC and additionally for use in Zones 20, 21 and 22 for Dust Groups IIIA, IIIB and IIIC. Also certified for Zone and Division installations for use with Marine Shipboard and Tray Cables under the NEC and CEC. They provide a controlled Ex db & IP displacement seal on the cable inner sheath an environmental seal on the outer sheath and “CROCLOCK®”, a unique non reversible multi clamping system for wire, braid and tape armoured cables. The gland maintains IP66 & IP68 to 50 metres and is deluge proof without the use of an additional seal. It is supplied with an IP O- ring seal as standard on metric entry threads. Options are available for use with lead sheath, LSOH cables and extreme temperature applications.
16 M20 x 1.5 1/2” or 3/4” 16 3.4-8.4 8.4-13.5 6.7-10.3
16H M20 x 1.5 1/2” or 3/4” 16 3.4-8.4 11.5-16.0 9.4-12.5
20S M20 x 1.5 1/2” or 3/4” 16 7.2-11.7 11.5-16.0 9.4-12.5
20 M20 x 1.5 1/2” or 3/4” 16 9.4-14.0 15.5-21.1 12.0 17.6
25 M25 x 1.5 3/4” or 1” 16 13.5 20.0 20.3 27.4 16.8 23.9
32 M32 x 1.5 1” or 1 ¼” 16 19.5 26.3 26.7 34.0 23.2 30.5
40 M40 x 1.5 1 ¼” or 1 ½” 16 23.0 32.2 33.0 40.6 28.6 36.2
50S M50 x 1.5 1 ½” or 2” 16 28.1 38.2 39.4 46.7 34.8 42.4
50H M50 x 1.5 1 ½” or 2” 16 28.1 38.2 45.7 53.2 41.1 48.5
50 M50 x 1.5 2” 16 33.1 44.1 45.7 53.2 41.1 48.5
63S M63 x 1.5 2” or 2 ½” 19 39.2 50.1 52.1 59.5 47.5 54.8
63H M63 x 1.5 2” or 2 ½” 19 39.2 50.1 58.4 65.8 53.8 61.2
63 M63 x 1.5 2 ½” 19 46.7 56.0 58.4 65.8 53.8 61.2
75S M75 x 1.5 2 ½” or 3” 19 52.1 62.0 64.8 72.2 60.2 68.0
75H M75 x 1.5 2 ½” or 3” 19 52.1 62.0 71.1 78.0 66.5 73.4
75 M75 x 1.5 3” 19 58.0 68.0 71.1 78.0 66.5 73.4
80 M80 x 2.0 3” or 3 ½” 25 62.2 72.0 77.0 84.0 71.9 79.4
80H M80 x 2.0 3” or 3 ½” 25 62.2 72.0 79.6 90.0 75.0 85.4
85 M85 x 2.0 3” or 3 ½” 25 69.0 78.0 79.6 90.0 75.0 85.4
90 M90 x 2.0 3 ½” or 4” 25 74.0 84.0 88.0 96.0 82.0 91.4
90H M90 x 2.0 3 ½” or 4” 25 74.0 84.0 92.0 102.0 87.4 97.4
100 M100 x 2.0 3 ½” or 4” 25 82.0 90.0 92.0 102.0 87.4 97.4
110 M110 x 2.0 4” 25 92.0 102.0 104.0 117.0
Peppers防爆格兰主要特点:
1、多用途解决方案(Peppers cable gland)
新的创新压盖样式,如A*RCC、A*RCM、A*RCF和LT-C,在导管安装中提供了更多的通用性。CR-S*M不同于市场上的任何其他压盖,被称为“导管塞盒”,可以有效阻止任何方向的爆炸。Peppers还将其的CROCLOCK®单向夹紧系统和雨淋保护概念集成到各种压盖设计中,确保完成更多安装时不会出错。
2、减少安装时间和成本(Peppers cable gland)
Peppers的阻隔压盖采用Peppers T-1000化合物,仅需 小时即可将导体端接在设备内。四小时后,可以检查复合室,并给设备通电。我们创新的屏蔽室提供的电缆验收比我们竞争对手的设计平均大17%,允许使用更小的密封套,从而显著降低成本。
3、压盖和外壳配件(Peppers cable gland)
Peppers提供全套经批准的危险区域连接解决方案,以补充其广泛的腺体。流行的外壳配件包括适配器和变径接头、堵头、通气呼吸阀、直角螺纹适配器等,所有这些配件都有多种螺纹转换选项,例如公制、NPT和PG等。专用于Peppers压盖的压盖配件包括锁紧螺母、密封垫圈、锯齿垫圈、接地标签和护罩。无论您安装需要什么,我们都会为您提供服务。
• Gland size does not necessarily equate to the entry thread size.
• The IP O-ring seal is only available on metric entry threads.
IP washers can be supplied for tapered entry threads.
• Dimensions (A) & (B) may differ for glands with non metric entry threads.
Please refer to our “Thread Reference Tables” for specific dimensions.
• Assembly instructions must be read prior to installation and adhered to in full.
• Peppers supply products with parallel entry threads that conform to the
flameproof threaded joint requirements of IEC/EN 60079-1 and other equivalent
standards. They usually incorporate a thread run out according to the available
machining techniques and will not have a full form thread for the entire length
Peppers Cable Glands Limited will not be held responsible for clients’
installations where this has not been taken into account.
• When selecting IP Washer & Shroud material for use with glands, please be aware of the
accessories temperature range to ensure they are suitable for the intended installation.
• Where approval in addition to ATEX, IECEx and CSA is required, this must