Output Current | 200mA minimum into 2ohm |
Test Voltage (o/c) | 9V DC nominal |
Test Duration (Class I Test) | 2s nominal |
Display Range | 0.01ohm to 19.99ohm |
Pass Value (Class I Test) | 0.2ohm |
Test Voltage | 250/500VDC @1mA nominal, < 2mA (s/c) |
Test Duration (Class I or II) | 2s |
Display Range | 0.01Mohm to 19.99Mohm |
Pass Value | 1.0MOhm Class I |
2.0MOhm Class II |
Test Voltage | 40V Nominal AC 50Hz Open Circuit |
Test Duration | 2s |
Display Range | 0.1mA to 19.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default)/0.25mA CL II |
Test voltage | 5V DC nominal |
Test Duration | Time for test (2s max) |
Test | Live/Neutral Checks for o/c, s/c and crossed |
Test Voltage | Supply Voltage, max current 13A |
Test Duration | 120s maximum |
Display Range | 0.15mA to 9.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default) |
Test Voltage | Supply Voltage, max current 13A |
Test Duration | 120s maximum |
Display Range | 0.10mA to 3.50mA |
Pass Value | 0.25mA |
*Requires 3 phase adaptor accessory | |
Test Voltage | 3 phase supply voltage |
Test Duration | Continuous measurement |
Display Range | 0.10 mA to 9.99 mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default) |
Test Voltage | Mains supply voltage |
Test Current | 30mA/150mA rms sinusoida |
Test Current Phase | 0°/180° auto switched on alternate tests |
Measuring Range | 0ms – 500ms |
Pass Value | 200ms |
Input voltage range | 225 – 254VAC max current 13A UK |
Indicates configuration of voltage potential: | Line potential phase to earth Line potential phase to neutral Line potential neutral to earth |
Memory size: | 999 test records |
Power source: | 6 x AA batteries |
Part number: | 403A910 |