Plug 'n' Play PAT Testing
The Apollo 500 is an advanced downloading PAT tester built for speed, accuracy and reliability of results with an on board memory for 10,000 complete test records. The Apollo 500 offers a complete solution to PAT testing to the IET 4th Edition Code of Practice; as well as remote data transfer, USB upload and download and an electrical risk assessment tool to help determine risk-based retest periods. The Apollo 500 is the perfect addition for those looking to upgrade from the Europa Plus Tester.
Key Features
- High definition colour display
- Store 10,000 appliance records
- Remote data transfer from field to office
- Bluetooth connectivity
- Risk-based suggested retest period calculator tool
- User tests for non-electrical tests and inspections
- Point to point measurement
- Low current earth continuity test guaranteeing accurate measurement
Earth Continuity
Test Current | +/- 200mA DC |
Display Range | 0.01 – 19.99Ω |
Pass Value | User Defined |
Insulation Resistance
Test Voltage | 500V / 250V DC @ 1mA nominal |
Display Range | 0.01MΩ - 19.99MΩ |
Pass Value | User Defined |
IEC Lead Test
Test Voltage | 5V ac nominal |
Test | Live / Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current/Load
Test Voltage | Supply voltage, maximum load current 16A |
Display Ranges | 0.01mA to 19.99mA |
Pass Value | User Defined |
Touch Current
Test Voltage | Supply Voltage, maximum load current 16A |
Display Ranges | 0.00 – 3.50mA |
Pass Value | User defined |
Load Power/Current
Test Voltage | Supply Voltage, maximum load current 16A |
Test Duration | Programmable up to a maximum of 255s depending on load. i.e. max duration is reduced for high loads. |
Display Range | 0.00kVA – 4.00kVA 0.00A – 16.00A |
Alternative Leakage Current
Test Voltage | >25Vac <50Vac |
Display Range | 0.00mA to 19.99mA |
Pass Value | User Defined |
RCD Test
Test Voltage | 230V +10%, -15% |
Test Current | 30mA / 150mA rms sinusoidal |
Display Range | 0ms - 2000ms |
Test method | Internal isolation to avoid tripping distribution board RCD |
Power Socket Test
Voltage Range | 207V – 253Vac |
Indicates configuration of voltage potential:- | |
Line potential phase to earth | |
Line potential phase to neutral | |
Line potential neutral to earth | |
General
Memory size | 10,000 Records |
Weight | 1.5kg |
Dimensions | 230mm x 150mm x 100mm |
Power Source | Mains or rechargeable battery pack |