Hawke防爆连接器Hawke Power Ex connector
Hawke防爆连接器Hawke Power Ex connector
上海颐品自动化,:

详细介绍

Hawke防爆连接器Hawke Power Ex connector
Hawke防爆连接器Hawke Power Ex connector
上海颐品自动化,:

Hawke Power Ex connector

Hazardous Area Connector

Tamb: -40°C to +60°C. ex logo II2 GD Exdb IIC Extb IIIC Db T85 IP66, 67 & DTS01 deluge protected.

Overview

The Powerex logo range of connectors have been designed specifically for the extremely demanding requirements of higher power applications.

Inserts are available with 1 to 4 contacts with a conductor acceptance range of between 50mm2 and 630mm2 operating up to 780A and 750V as standard. Other voltages available on special request.

Powerex logo Connector Dimensions

PowerEx Connector Dimensions

For connector plugs and connector receptacles, cable glands are required to terminate incoming cables. These can be selected from the cable gland section of our website. These cable glands include but are not restricted to 501/453/Universal and the ICG 653/Universal.

DIMENSIONS (MM)
DimensionEx32PEx40PEx50PEx63PEx75P
A228228228228238
B168168168168178
ØC60667689101
ØD737989102114
E251251251251261
ØF677382.595108
ØP4855657890
R6060606060
S75.575.575.575.576
ØT61687790102
U68.568.568.568.568.5
Thread V (1.5mm Pitch)M32*M40*M50*M63*M75*
ØW100106116129141
X184184184184194
* Other entry threads available upon request.

Powerex logo Inserts

PowerEx Connector Inserts

INSERT SELECTION TABLE
Configuration
Shell Size 32Shell Size 40Shell Size 50Shell Size 63Shell Size 75
1 x 50mm² + Earth1 x 185mm² + Earth3 x 50mm² + Earth3 x 95mm² + Earth3 x 185mm² + Earth
1 x 70mm² + Earth1 x 240mm² + Earth3 x 70mm² + Earth3 x 120mm² + Earth3 x 240mm² + Earth
1 x 95mm² + Earth-4 x 50mm² + Earth3 x 150mm² + Earth4 x 185mm² + Earth
1 x 120mm² + Earth-4 x 70mm² + Earth4 x 95mm² + Earth4 x 240mm² + Earth
1 x 150mm² + Earth-1 x 185mm² + Earth4 x 120mm² + Earth1 x 500mm² + Earth
--1 x 240mm² + Earth4 x 150mm² + Earth1 x 630mm² + Earth
---1 x 300mm² + Earth-
---1 x 400mm² + Earth-
All Hawke Powerex logo Connectors have a maximum working voltage of (750V AC).
Other voltages and contact configurations also available contact us for details.

Powerex logo Calculations

To select the shell size of the connector, it is essential that you calculate the dissipated wattage of the arrangement. This ensures that the arrangement does not exceed the maximum permitted temperature classification with regard to the upper ambient temperature for the area of installation. (please refer to table 1 below for the maximum allowable dissipated wattage per connector size).

TABLE 1
Connector SizeUpper Ambient
Temperature of +40°C
Upper Ambient
Temperature of +50°C
Upper Ambient
Temperature of +60°C
Temperature ClassTemperature ClassTemperature Class
T6T5T6T5T6T5
Ex32P20.5W27.5W15.75W26W7.5W15.75W
Ex40P22.5W30.5W17.5W28W8.7W17.5W
Ex50P25.8W35.3W20W32.25W10W20W
Ex63P30.2W41.5W23.5W37.7W11.7W23.5W
Ex75P36.3W49.5W28.25W45.25W14W28.25W
 Maximum allowable dissipated wattage
Other ambient temperature options can be extrapolated from
table 1 above, or contact Hawke International for more information.
TABLE 2
Contact SizeCombined Cable And Contact Resistance (Ohms)Contact Current Rating
50mm²514190 amps
70mm²387240 amps
95mm²283290 amps
120mm²239340 amps
150mm²202385 amps
185mm²170440 amps
240mm²144520 amps
300mm²82590 amps
400mm²67670 amps
500mm²54720 amps
630mm²45780 amps

Dissipated Wattage Calculation

Equation definitions:

W = Dissipated wattage factor of the connector

N = The number of conductors to be terminated/number of contacts required. (Note: A contact comprises of a pin and socket).

I = The current requirement per contact. (Note: This must be equal to or less than the maximum current rating of the contact, as shown in table 2 above).

R = The combined cable and contact resistance (see table 2 above).

Values pertinent to these definitions must then be input into the relevant fields below to calculate the dissipated wattage (W) of your chosen arrangement:

1. W = N x I ² x R
NIRDissipated Wattage
(Watts)
W
    
 

Note: The result must be lower than the maximum figure shown in table 1 above, for the appropriate temperature class and ambient temperature).

e.g. T6 40°C ambient application with 4 x 95mm² conductors running at 160 amps.
N = 4 contacts
I = 160 amps
R = 0.000283 ohms (95mm² soldered combined cable and contact resistance)

Therefore W = 4 x 25600 x 0.000283 = 28.9 watts.
Therefore an Ex63P Connector should be specified for this application as the shell size can accommodate the required 4 x 95mm² pin / socket inserts (see insert selection table) and the resultant dissipated wattage (28.9 watts) is below the maximum permitted 30.2 watts (see table 1 above).

This equation can also be transposed to facilitate the calculation of the maximum number of conductors permitted in your selected connector (calculator 2 below ) and the maximum allowable current within the upper ambient temperature of your location (calculator 3 below).

2. number of conductors formula
WRIMaximum Number Of
Conductors
N
    
 
3. maximum current formula
WNRCurrent
(Amps)
I
    
 
Note: The result must not exceed the maximum current rating of the contacts (see table 2 above)

Note: Unless otherwise requested, connectors will be marked as T5 with an upper ambient temperature of +40°C.

Order Codes

When ordering, select the relevant code from each block as shown in the example below:
Powerex logo/Exd-50-S-CR-A-4-50-S-FLFRC-A-1

Powerex logoSelect CodeDescriptionExample Code
ProtectionExdFlameproofExd
Shell Size323250
4040
5050
6363
7575
MaterialBBrass
Note: (for single core cables, Brass must be used)
S
SStainless Steel (as standard)
NNickel Plated Brass
Connector StyleCPConnector PlugCR
CRConnector Receptacle
BRBulkhead Receptacle
Internal Earth Size
Note: Should be at least 50% of phase conductor size
A50mm²A
B70mm²
C95mm²
D120mm²
E150mm²
F185mm²
G240mm²
Number Of Contacts See insert selection 
Contact Type Contact TypeMaximum Conductor Acceptance Diameter (mm)50
5050mm²9.5
7070mm²11.5
9595mm²13
120120mm²14.5
150150mm²16.5
185185mm²18.5
240240mm²20.5
300300mm²25
400400mm²29
500500mm²32
630630mm²38
XNo Insert
Insert TypePPinS
SSocket
Accessories
* Note: only the connector receptacle (CR) can be flange mounted.
FLMounting Flange *FLFRC
FPCFlameproof Plug Cap
FRCFlameproof Receptacle Cap
PPCEnvironmental Plug Cap
PRCEnvironmental Receptacle Cap
CertificationAATEX/IECEx/EAC/INMETROA
NATEX/IECEx/EAC/INMETRO /NEC 505
Voltage reduced to 600V
Ambient Rating & Temperature Class
T5 +40°C will be supplied as standard if alternative not specified
1T5 +40°C Standard1
2T5 +50°C
3T5 +60°C
4T6 +40°C
5T6 +50°C
6T6 +60°C

Find A Connector Modifier

Ordering Information

For ordering information and codes, please see order codes tab.

 

 

 

 

 

 

 