技术参数: | 过载特性 1、 SI:标准反时限 2、 VI:快速反时限 3、 EI(G):特快反时限(一般配电机保护用) 4、 EI(M):特快反时限(电机保护用) 5、 HV:高压熔丝兼容 I2T:通用型反时限保护
六种长延时保护动作延时时间(常规值,前五种是无级可调的)
曲线类型 | 故障电流 | 动作时间(s) | 系数K= | 0.005 | 0.008 | 0.012 | 0.02 | 0.03 | 0.04 | 0.05 | 0.06 | 0.075 | SI | 1.5Ir | 0.61 | 0.98 | 1.47 | 2.46 | 3.68 | 4.91 | 6.14 | 7.37 | 8.29 | 2Ir | 0.36 | 0.57 | 0.86 | 1.43 | 2.15 | 2.87 | 3.58 | 4.3 | 5.37 | 6Ir | 0.14 | 0.22 | 0.33 | 0.55 | 0.82 | 1.1 | 1.37 | 1.64 | 2.06 | 系数K= | 1 | 1.6 | 2.4 | 4 | 6 | 8 | 10 | 11 | 13.5 | VI | 1.5Ir | 2 | 3.2 | 4.8 | 8 | 12 | 16 | 20 | 22 | 27 | 2Ir | 1 | 1.6 | 2.4 | 4 | 6 | 8 | 10 | 11 | 13.5 | 6Ir | 0.2 | 0.32 | 0.48 | 0.8 | 1.2 | 1.6 | 2 | 2.2 | 2.7 | 系数K= | 10 | 16 | 24 | 40 | 60 | 80 | 100 | 115 | 135 | EI(G) | 1.5Ir | 8 | 12.8 | 19.2 | 32 | 48 | 64 | 80 | 92 | 108 | 2Ir | 3.32 | 5.33 | 8 | 13.32 | 20 | 26.66 | 33.3 | 38.33 | 45 | 6Ir | 0.29 | 0.46 | 0.7 | 1.16 | 1.74 | 2.32 | 2.9 | 3.29 | 3.92 | 系数K= | 10 | 16 | 24 | 40 | 60 | 80 | 100 | 115 | 135 | EI(M) | 1.5Ir | 6.22 | 9.96 | 14.9 | 24.9 | 37.3 | 49.8 | 62.2 | 71.56 | 84 | 2Ir | 2.94 | 4.72 | 7.06 | 11.78 | 17.68 | 23.58 | 29.46 | 33.88 | 39.78 | 6Ir | 0.28 | 0.45 | 0.68 | 1.13 | 1.69 | 2.26 | 2.82 | 3.24 | 3.81 | 系数K= | 10 | 16 | 24 | 40 | 60 | 80 | 100 | 115 | 135 | HV | 1.5Ir | 2.46 | 3.94 | 5.9 | 9.85 | 14.8 | 19.7 | 24.6 | 28.29 | 33.2 | 2Ir | 0.66 | 1.06 | 1.60 | 2.66 | 4.00 | 5.32 | 6.66 | 7.66 | 9.00 | 6Ir | 0.01 | 0.01 | 0.02 | 0.03 | 0.05 | 0.06 | 0.08 | 0.09 | 0.11 | I2T | 1.5Ir | 15 | 30 | 60 | 120 | 240 | 480 | | | | 2Ir | 8.4 | 16.9 | 33.8 | 67.5 | 135 | 270 | | | | 6Ir | 0.94 | 1.88 | 3.76 | 7.52 | 15.04 | 30.08 | | | | 曲线类型 | 故障电流 | 动作时间(s) | 系数K= | 0.09 | 0.12 | 0.14 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | SI | 1.5Ir | 11.1 | 14.7 | 17.2 | 24.6 | 36.8 | 49.1 | 61.4 | 73.7 | 86 | 2Ir | 6.45 | 8.6 | 10.03 | 14.33 | 21.49 | 28.65 | 35.82 | 42.98 | 50.15 | 6Ir | 2.47 | 3.29 | 3.84 | 5.48 | 8.22 | 10 | 13.7 | 16.4 | 19.2 | 系数K= | 18 | 25 | 28 | 40 | 60 | 80 | 100 | 120 | 140 | VI | 1.5Ir | 36 | 50 | 56 | 80 | 120 | 160 | 200 | 240 | 280 | 2Ir | 18 | 25 | 28 | 40 | 60 | 80 | 100 | 120 | 140 | 6Ir | 3.6 | 5 | 5.6 | 8 | 12 | 16 | 20 | 24 | 28 | 系数K= | 180 | 250 | 280 | 400 | 600 | 800 | 1000 | 1200 | 1300 | EI(G) | 1.5Ir | 144 | 200 | 224 | 320 | 480 | 640 | 800 | 960 | 1120 | 2Ir | 60 | 83.33 | 93.32 | 133 | 200 | 266 | 333 | 400 | 433 | 6Ir | 5.22 | 7.14 | 8.12 | 11.6 | 17.4 | 23.2 | 29 | 34.8 | 37.7 | 系数K= | 180 | 250 | 280 | 400 | 600 | 800 | 1000 | 1200 | 1300 | EI(M) | 1.5Ir | 112 | 155 | 174 | 249 | 373 | 498 | 622 | 747 | 871 | 2Ir | 53.04 | 73.67 | 82.52 | 117 | 176 | 235 | 294 | 353 | 383 | 6Ir | 5.08 | 7.06 | 7.9 | 11.3 | 16.9 | 22.6 | 28.2 | 33.9 | 36.7 | 系数K= | 180 | 250 | 280 | 400 | 600 | 800 | 1000 | 1200 | 1300 | HV | 1.5Ir | 44.3 | 61.53 | 68.9 | 98.5 | 147 | 197 | 246 | 295 | 344 | 2Ir | 12 | 16.67 | 18.66 | 26.66 | 40.00 | 53.32 | 66.66 | 80 | 86.66 | 6Ir | 0.14 | 0.19 | 0.22 | 0.31 | 0.46 | 0.62 | 0.77 | 0.93 | 1 | 技术数据 1、 过载长延时 项目 | 参数 | 备注 | 电流整定范围(Ir) | Ir=(0.4~1.0)×In+开、关 | 开、关为开关保护 | 动作特性 | I≤1.05Ir,2h不动作 I≥1.3Ir,<1h动作 | zui大反时限延时(秒) | 特性曲线 | 多条曲线可整定,出厂是整定为曲线EI(G) | | 曲线速率 | IEC255标准,共80级点,可整定 | | 精度 | ±10% | | 热记忆 | 30min | 复位或断电自动清除 | N相整定 | 0.5Ir,1.0Ir可整定+OFF | 2、 短路短延时 短延时保护有两种方式,一种为反时限保护,当故障电流超过反时限设定值时,控制器按与过载一样的曲线进行延时保护,仅是保护的速度要快10倍(即按过载曲线函数算出的故障延时时间的十分之一);另一种为定时限保护,当故障电流超过定时限设定值时,控制器按定时*延时保护。 项目 | 参数 | 备注 | 电流整定范围(Isd) | Isd=(1.0~15) ×Ir+开、关 | 开、关为开关保护 | 动作特性 | I≤0.9Isd不动作 I≥1.1Isd动作 | 定时限 | Tsd | 0.1~1s(0.1级差) | | 精度 | ±10% | 反时限特性 | 曲线同过载长延时,但曲线速度快了10倍 | | 热记忆 | 15min | 复位或断电自动清除 | 3、 短路瞬时保护 瞬时保护动作时间(含断路器固有的分断时间)应小于30ms。 项目 | 参数 | 备注 | 电流整定范围(Ii) | Ii=1.0In~50KA+开、关 | 开、关为开关保护 | 动作特性 | I≤0.85Ii,不动作 I≥1.15Ii,瞬时动作 | | 4、 地故障保护 项目 | 参数 | 备注 | 电流整定范围Ig | (0.2~1.0)×In,无级可调 | 开、关为开关保护 | 动作特性 | ≤0.9Ig,不动作 ≥1.1Ig,延时动作 | 整定时间Tg | 定时限 | 整定时间(ms) | 0.1S到1S无极可调 | 反时限 | 整定时间(ms) | - | 100 | 200 | 300 | 400 | |