The MultiTox DMI-TT6 range of detectors are available for a wide range of toxic gases, and is known for its excellent selectivity. For some applications, electrochemical cells are the only solution. The MultiTox DMI-TT6 is also available for Oxygen detection, and is used in several demanding solutions.
The DMI-TT6 and DMI-TO6 are constructed from a common housing and electronics with the detection properties being determined by the type of sensor (cartridge) used. A wide range of cells are available, including hydrogen sulphide, ammonia and carbon monoxide to name a few. The cells are intrisically safe, and may be replaced with the detector powered. This versatile housing is also used for our flammable (catalytic) gas detector as well our semiconductor (MOS) detector - although these units are certified flameproof, not intrinsically safe - see separate datasheet.
The intelligent, microprocessor driven unit is fully configurable using a wireless handheld terminal (TLU) giving true flexibility to the installer. Elements such as relay operation and alarm levels are all set via the TLU, hazardous area approved handheld unit.
The device offers a wide range of output options as standard and is suitable for use in SIL 2 applications. The unit may be interfaced directly with a wide range of panels, controllers and PLC’s etc.
The DMI-TT6 and DMI-TO6 may be used in refineries, offshore driling and production platforms, processing and storage plants as well as chemical plants.
技术参数:
GENERAL | |
Type | Gas detector |
Product | Simtronics MultiTox, H2S (EC) |
Product code | DMI-TT6-31** |
Manufacturer | Simtronics |
GAS DETECTOR | |
Type | Electrochemical cell |
Detected gas | Hydrogen Sulphide (H2S) |
Calibrated range | 20ppm, 50ppm, 100ppm, 200ppm (variants) |
PERFORMANCE | |
Accuracy | ±5% of calibrated range |
Linearity | ±2% |
Repeatibility | ±1% |
Stability | ±1% (zero point) |
Response time | T50: <30 sec, T90: <120 sec |
Calibration interval | 3 months (calibration check) |
Sensor life | 24 months |
ELECTRICAL | |
Power supply | 24V DC, range (18 - 32V DC) |
Power consumption | 30 mA normal; 180 mA during heating |
Cable entry | 2x M20, one entry with Exd plug |
Junction box | “No-touch” field cabling”, detector replaceable without opening cable glands |
Connection | 0.3 mm2 (22 AWG) - 1.5 mm2 (16 AWG), 3 or 4 wires |
Analogue output signal | 0-20mA, source, max. load impedance 700Ω. |
Fault signalling | Diagnosis signalling in the 2.0 - 3.4mA range |
Relays | 2 configurable relays for alarm and fault |
Maintenance interface | Wireless (IR) handheld terminal for configuration, test and diagnosis |
ENVIRONMENT | |
Storage | -40°C to +70°C (-40°F to 158°F) |
Operation | -20°C to +50°C (-4°F to 122°F) |
ATEX | -40°C to +60°C (-40°F to 140°F) |
Humidity | 95% RH (non-condensing) |
Ingress | IP66 |
RFI/EMI | Complies with EN50081-1, EN50081-2, EN50082-1 and EN50082-2. |
HOUSING | |
Ex Classification | Ex d ia II C T6 |
Material | Epoxy coated aluminium or Stainless steel (Specify variant) |
Weight | Aluminium: 1.8 Kg (4.0 lbs) Stainless steel: 6.5 Kg (14.3 lbs) |
Dimensions | 165H x 118D x 184W (mm), 6.50H x 4.65D x 7.25W (inches) |
APPROVALS | |
ATEX | Certificate DM LCIE 03 ATEX 6262 |
ACCESSORIES | |
TLU600 | Infrared remote control unit |
AS008-200 | Sunshade |
AS005 | Calibration cup |
AS011-2-X | Sample flow housing |
AS019 | Splash guard |
Product Sheet MultiTox DM TT6338.12 KB
Operating Manual MultiTox Detector2.13 MB
Operating Manual Remote Controller TLU 600/6102.93 MB
证书:
ATEX Certification402.79 KB
应用:
Chemical Plants
Pharmaceutical Plants
Auto Industry
Onshore/Offshore Oil & Gas Platforms
Storage of Toxic Materials