品牌
其他厂商性质
所在地
The Cooper MEDC-Hawco heat detector has been designed for use in hazardous environments. These units are suitable for fire alarm and/or suppression systems in offshore and onshore applications including paint spray booths, flammable material stores, turbine rooms, extract ductwork and other hazardous areas throughout the oil & gas, petrochemical and process industries.
Comprising a Fenwal rate-compensated detector with all-stainless steel external construction, mounted to either a type SM87 marine grade alloy enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Exia, Exem/UL versions). The contact in the detector CLOSES at alarm temperature.
To select appropriate temperature setting see specification on reverse.
*Model dependent.
Certification | ATEX, UL, GOST ‘R’ & ‘K’, Russian Fire Approval,CQST, Inmetro, ABS |
Flameproof | ATEX Ex II 2G, Exd IIB T6 |
Area Classification | Zone 0, Zone 1 and Zone 2 use. |
Increased Safety | ATEX Ex II 2G, Exem II T6 |
Intrinsically Safe | ATEX Ex II 1G, Exia IIC T6 |
Certified Ambient Temperature | -20°C to +125°C Exd (T3) ATEX/GOST ‘R’ |
-20°C to +55°C Exd (T6)/Exem | |
-55°C to +55°C Exia | |
Ingress Protection | IP66 & IP67 |
Material | Marine Grade Alloy (Exd) |
Corrosion-free GRP (Exia/Exem) | |
Temperature Settings | 140°F to 725°F (60°C to 385°C) |
Entries | 2 x 20mm |
Weight | 1.1-2.0kg (model dependent) |
Options | Enclosures, guard, colour, tag and duty labels, |
temperature setting. Series and EOL resistors, | |
blanking plugs. |