400系列安全调节阀

400系列安全调节阀400系列安全调节阀

参考价: 面议

具体成交价以合同协议为准
2023-02-28 07:36:21
109
产品属性
关闭
上海美盛自动化设备有限公司

上海美盛自动化设备有限公司

免费会员
收藏

组合推荐相似产品

产品简介

400系列安全调节阀400系列调节阀与非流动试点,采用了*的中试阀的设计。工艺条件下,无论是飞行员和主阀拧紧,以高达百分之98的设定压力。

详细介绍

400系列安全调节阀
400系列调节阀与非流动试点,采用了*的中试阀的设计。工艺条件下,无论是飞行员和主阀拧紧,以高达百分之98的设定压力。

Series 400 Modulating Safety Relief Valve

  • Description
  • Specifications
  • Documentation

The Series 400 modulating valve, with non-flowing pilot, incorporates an advanced design in pilot operated valves. Under process conditions, both pilot and main valve can be tight to as high as 98 percent of set pressure. The main valve lifts proportionally according to demand, restricting product loss to only what needs to be relieved to prevent process pressure from exceeding the code allowance.

The Series 400 valve is well suited for gas and/or liquid services, including dirty and/or wet services. The modulating action is strongly preferred for liquid relief because it eliminates the destructive effects of “liquid hammer.”

Features & Benefits:

  • Unique Field Test Capability – Allows accurate set pressure verification with valve in service. No system isolation valve or rupture disc required. All field test connections are provided with an indicator for accurate and easy set pressure testing.
  • Reduced Product Loss and Pollution – Soft seats for premium tightness before and after relief cycles. Modulating action relieves minimum product to prevent overpressur.
  • ASME Section VIII Code Stamp – Certified National Board capacities for both gas and liquid service assures user of independent third party flow rate verification.
  • Non-flowing Pilot – Minimizes entrance of dirt and formation of hydrates in pilot. Due to low velocities within the pilot and supply tubing, most particles will drop out upstream of pilot inlet screen. Optional cartridge type pilot filter is available for extremely dirty services.
  • Rugged Bracket Pilot Mounting – Extremely rigid mounting protecting against vibration and careless handling. Shake table proven.
  • Reduced Noise – Modulating action minimizes flow and resultant noise during normal system upset, reducing noise abatement costs.
  • Increased System Output – Because of valve tightness to 98 percent of set pressure, the system can be operated nearer set pressure without valve leakage, resulting in greater system throughput.
  • Reduced Maintenance Costs – Soft seats greatly extend service life, making costly and time-consuming metal seat lapping unnecessary.
  • Ease of Adjustment – Single adjustment for set pressure allows accurate and dependable setting.
  • Balanced Design – Proper valve operation and lift are unaffected by back pressure. Costly and fragile metal bellows are not required.
Specifications

Orifice Sizes: D through T, Full bore valves also available
Connections: 1" x 2" to 8" x 10"
Inlet Flange Ratings: ANSI 150, 300, 600, 900, 1500, 2500
Temperature Range: -65°F to +500°F [-54°C to +260°C]
Minimum Pressure: 15 psig [1.03 barg]
Maximum Pressure: 1,480 psig [102 barg]



上一篇:自力式压力调节阀的安装步骤和注意事项有哪些 下一篇:自力式压力调节阀的优缺点分别是什么
热线电话 在线询价
提示

仪表网采购电话