品牌
代理商厂商性质
所在地
渗碳炉, 陶瓷窑 直接连接到氧化锆探头 碳势控制, 氧百分含量,露点 CO 或 H2 补偿 探头结垢处理, 探头维护, 探头清洁 Modbus®, Profibus®, 或 DeviceNet™ 通讯 PID控制 ,阀位控制和直流DC重发 |
The 2404 Atmosphere Controllers provide accurate display and control of carbon level in carburizing furnaces and ceramic glazing kilns. There are three different controllers that connect to a variety of common zirconia probes, including the Series AP from Eurotherm, which measure the % oxygen in a furnace. The carbon level is calculated from two inputs, the % O2 and temperature measured by the probe. An optional third input can accept a signal from a CO or H2 analyzer, thus providing a more precise carbon or dewpoint measurement. In addition to carbon levels, the controller can be configured to measure % O2, log O2, dewpoint (°C or °F) and probe millivolts. A probe clean output forces compressed air through the probe at regular intervals to burn off soot. A sooting alarm will warn if carbon deposits | build up to give false readings. Health of the probe is measured by monitoring the time it takes the probe mV reading to recover from self-clean. Probe clean and CO/H2 compensation are enabled by digital inputs. ESO209 - This low cost version offers PID and two module slots plus Modbus® or ASCII communications. |