国标zc-yjv32 8.7/10kv-3*185高压电力电缆
6kV~35kV 中低压铜芯及铝芯交联聚乙烯绝缘电力电缆(YJV电缆,YJV22电缆,YJLV电缆,YJLV22电缆)XLPE Insulated Power Cable |
交联聚乙烯绝缘电力电缆是采用化学方法或物理方法,使聚乙烯分子由线型分子结构转变为三维网状结构,由热塑性的聚乙烯变成热固性的交联聚乙烯,从而提高了聚乙烯的耐老化性能、机械性能和耐环境能力,并保持了优良的电气性能。 交联聚乙烯绝缘电力电缆导体的允许长期高温为90摄氏度,较低绝缘电缆、聚氯乙烯绝缘电缆和聚乙烯绝缘电缆高,且具有重量轻、结构简单、使用方便、耐化学腐蚀和敷设不受落差限制等优点。 26/35KV电力电缆,18/30KV交联电缆,12/20KVYJV电缆,8.7/15KVYJV22电缆线,6/10KV铝芯交联电缆线,3.6/6KVYJLV单芯电缆 中低压交联电缆产品标准 Standard 本产品按GB12706《额定电压35V及以下铜芯、铝芯塑料绝缘电力电缆》标准生产,同时还可根据用户需要按电工委员会推荐标准IEC、英国标准、德国标准及美国标准生产。 The product is manufactured according to the standard of《GB12706 or IEC、BS、DIN and ICEA upon request. 适用范围 Applications 本产品适用于工频额定电压3.6/6kv~26/35kv输配电线路作配送电能子用。 The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv. 使用特性 Operating characteristics · 工频额定电压U0/U为3.6/6kv~26/35kv。 Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv. · 电缆导体的高允许工作温度:90℃。 Max.admissible operating temperature of the conductor:90℃. · 短路时(长时间不超过5s)电缆导体的高温度不超过2500C。 Max. short-circurt temperature of conductor shall not exceed 2500C. (5s maximum duration) · 电缆敷设时环境温度应不低于00C。 The ambient temperature under installation should not below 00C. · 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。 The bending radius of a single-core cable should not less than 20 times of the cable diameter. The bending radius of a single-core cable should not less than 15 times of the cable diameter. 电缆额定电压的选择 Voltage designation · 电缆的额定电压应适合于电缆系统的运行状况,用U0/U(Um)kv表示。 U0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压; U-电缆设计用的导体间的额定工频电压; Um-设备可承受的“高系统电压”的大值。 The rated voltage of the cable for a given applixation shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of U0/U(Um)kv Where: U0-The rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed; U - The rated power-frequency voltage between conductos, for which the cable designed; Um- The maximum value of the“highest system voltage”for which the equipment may beused. · 三相系统用电缆的U0值推荐如下表: The values of U0 recommened for cable to be used in three-phase systems are listed below: 国标zc-yjv32 8.7/10kv-3*185高压电力电缆 |
U kv | U m kv | U 0 * kv | A 和 B 类系统 System categories A and B | C 类系统 Systems categories C | 6 | 7.2 | 3.6 | 6 | 10 | 12 | 6 | 8.7 | 15 | 17.5 | 8.7 | 12 | 20 | 24 | 12 | 18 | 30 | 36 | 18 | - | 35 | 40.5 | 21 | 26 |
|
A类系统──该类系统任何一相导体与地和接地导体接触时,能在1min内与系统分离 B类系统──该类系统仅包括单相接地故障短时运行的条件,接地故障时间应不超过1h, 但在任何情况下,长不超过8h每年接地故障总持续时间不超过125h; C类系统──不属于A类、B类的系统。 System category A──This category comprises those systems in which any phase conductor that comes in contact with earth or an earth conductor. is disconnected from the system within 1 min. System category B ──This category comprises those system which,under faultconditions,are operated,are operated for ashorttimewith one phase earthed.This period should not exceed 1 h..Fora longer period, not exceeding 8h on any occasion, can be tolerated.The total duration of earth faults in any year should not exceed 125h. System categeory C──This category comprises all systems which do not fall into A and B 电缆的型号Type of cable |
型号 Type | 名称 Designation | 适用范围 Application | YJV | 铜芯交联聚乙烯绝缘氯乙烯护套电力电缆 Copper conductor,XLPE insulated and PVC sheathed power cable | 室内、隧道及电缆沟等场所,不能承受机械外力。单芯电缆不允许敷设在磁性管道中。 For laying indoors 、 intunnel or cable trench,unable to bear external mechan-icalforces.Single-core cable in magnetic duct is not permissible | YJLY | 铝芯交联聚乙烯绝缘乙烯护套电力电缆 Aluminium conductor, XLPE insulated and PVC sheathed power cable | YJY | 铜芯交联聚乙烯绝缘氯乙烯护套电力电缆 Copper conductor ,XLPE insulated and PEsheathed power cable | YJLY | 铝芯交联聚乙烯绝缘氯乙烯护套电力电缆 Alumimium conductor ,XLPE |
|
产品介绍:高压交联电缆产品具有传输容量大,工作温度,不受落差的限制,安装敷设方便等特点,广泛应用于工矿企业和城市电网中。高压交联电缆主要用于电力、建筑、工矿、冶金、交通等部门的动力、照明输配电系统,由于聚乙烯是电绝缘性能的塑料,加上经过高分子交联后成为热固性材料,因此其电性能好,机械性能和耐热性好。近二十年来,已成为中国中、高压电缆的主导品种,产品适用于6——35KV的各个电压级中它可分为:YJV-交联聚乙稀绝缘聚氯乙烯护套电力电缆,YJV22-交联聚乙烯绝缘钢带铠装高压电缆,YJLV-交联聚乙烯绝缘铝芯钢带铠装高压电缆。
执行标准:GB/T12706-2002
使用特性
· 工频额定电压U0/U为6kv/10kv~26/35kv。
· 电缆导体的高允许工作温度:90℃。
· 短路时(长时间不超过5s)电缆导体的高温度不超过2500C。
· 电缆敷设时环境温度应不低于00C。
· 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。
电缆额定电压的选择
· 电缆的额定电压应适合于电缆系统的运行状况,用U0/U(Um)kv表示。
U0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压;
U-电缆设计用的导体间的额定工频电压;
Um-设备可承受的“高系统电压”的大值。
塑料电线电缆制造的基本工艺流程
1.铜、铝单丝拉制
电线电缆常用的铜、铝杆材,在常温下,利用拉丝机通过一道或数道拉伸模具的模孔,使其截面减小、长度增加、强度提高。拉丝是各电线电缆公司的首道工序,拉丝的主要工艺参数是配模技术。
2.单丝退火
铜、铝单丝在加热到一定的温度下,以再结晶的方式来提高单丝的韧性、降低单丝的强度,以符合电线电缆对导电线芯的要求。退火工序关键是杜绝铜丝的氧化.
3.导体的绞制
为了提高电线电缆的柔软度,以便于敷设安装,导电线芯采取多根单丝绞合而成。从导电线芯的绞合形式上,可分为规则绞合和非规则绞合。非规则绞合又分为束绞、同心复绞、特殊绞合等。
为了减少导线的占用面积、缩小电缆的几何尺寸,在绞合导体的同时采用紧压形式,使普通圆形变异为半圆、扇形、瓦形和紧压的圆形。此种导体主要应用在电力电缆上。
4.绝缘挤出
塑料电线电缆主要采用挤包实心型绝缘层,塑料绝缘挤出的主要技术要求:
4.1.偏心度:挤出的绝缘厚度的偏差值是体现挤出工艺水平的重要标志,大多数的产品结构尺寸及其偏差值在标准中均有明确的规定。
4.2.光滑度:挤出的绝缘层表面要求光滑,不得出现表面粗糙、烧焦、杂质的不良质量问题
4.3.致密度:挤出绝缘层的横断面要致密结实、不准有肉眼可见的针孔,杜绝有气泡的存在。
5.成缆
对于多芯的电缆为了保证成型度、减小电缆的外形,一般都需要将其绞合为圆形。绞合的机理与导体绞制相仿,由于绞制节径较大,大多采用无退扭方式。成缆的技术要求:一是杜绝异型绝缘线芯翻身而导致电缆的扭弯;二是防止绝缘层被划伤。
大部分电缆在成缆的同时伴随另外两个工序的完成:一个是填充,保证成缆后电缆的圆整和稳定;一个是绑扎,保证缆芯不松散。
6.内护层
为了保护绝缘线芯不被铠装所疙伤,需要对绝缘层进行适当的保护,内护层分:挤包内护层(隔离套)和绕包内护层(垫层)。绕包垫层代替绑扎带与成缆工序同步进行。
7.装铠
敷设在地下电缆,工作中可能承受一定的正压力作用,可选择内钢带铠装结构。电缆敷设在既有正压力作用又有拉力作用的场合(如水中、垂直竖井或落差较大的土壤中),应选用具有内钢丝铠装的结构型。
8.外护套
外护套是保护电线电缆的绝缘层防止环境因素侵蚀的结构部分。外护套的主要作用是提高电线电缆的机械强度、防化学腐蚀、防潮、防水浸人、阻止电缆燃烧等能力。根据对电缆的不同要求利用挤塑机直接挤包塑料护套。