免费会员 生产厂家
参考价:
具体成交价以合同协议为准
免费会员 生产厂家
Application | Compressors acc. IEC/EN 60335 |
Functions | Motor temperature static, Motor temperature dynamic, Short circuit |
Supply voltage | AC 115-240V |
Permitted ambient temperature | -30...+70°C |
Temperature measuring circuits: Type | 1-2 AMS sensors in series alternative 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total | <1.8kΩ |
Temperature measuring circuits: R_trip, static | 4.5kΩ ±20% |
Temperature measuring circuits: R_reset | 2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line | 30m |
Short circuit monitoring system PTC | Typically <30Ω |
Reset delay: Motor temperature static | 1min ±12s |
Reset delay: Motor temperature dynamic | 5min ±1min |
Reset of reset delay | Main reset >5s only possible if there is no error current |
Relay: Connection | Refer to wiring diagram Max. 2.5A C300 |
Relay: Mechanical service life | Approx. 1 million switching cycles |
Interface | Diagnose port (DP) |
Protection class acc. To EN 60529 | IP00 |
Connection type | Screw type terminal |
Housing material | PA glass-fibre-reinforced |
Mounting | Screw mounted |
Dimensions | Refer to dimensions in mm |
Weight | Approx. 150g |
Check base | IEC/EN 60335, IEC/EN 60730, UL 60730 EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval | UL File no. E75899 cURus VDE certification no. |