0.6/1kv聚氯乙烯交联聚乙烯绝缘耐火电力电缆 PVCXLPEInsulatedFire-Resistant Power Cable
产品标准
The product is manufactured according to the standard of GB12706GB12666 or IEC,BS,DIN,ICEA,and JIS upon request.
适用范围 本产品适用于工频额定电压0.6/1kV及以下配电线路或工业装置中有耐火要求的固定敷设场所使用。 The product is suitable for use in power distribution lines or fixed installations with rated power-frequency voltage up toincluding 0.6/1kV.
使用特性 ·工频额定电压U0/U:0.6/1kV。 Rated power-frequency voltage U0/U:0.6/1kV. ·电缆导体的zui高允许*工作温度(PVC/XLPE):70℃/90℃. Max.permissible continuous operating temperature of conductor PVC/XLPE: 70℃/90℃ ·短路时(zui长持续时间不超过5s)电缆导体zui高允许温度 PVC:导体截面≤300mm2-160℃ 导体截面>300mm2-140℃ XLPE:250℃ Max.short-circuit temperature of the conductor shall not exceed5s maxiumduration: PVC:cross-section of conductor≤300mm2-160℃ cross-section of conductor>300mm2-140℃ XLPE:250℃ ·电缆敷设时环境温度应不低于0℃ The ambient temperature under installation should not below 0℃ ·电缆的弯曲半径:多芯电缆不小于电缆外径15倍,单芯电缆不小于电缆外径20倍。 The bending radius of a single-core cable should not less than 20 times of the cable diameter. The bending radius of multicore-cable should not less than 15 times of the cable diameter.